PhaseTapChangerNonLinear
The non-linear phase tap changer describes the non-linear behaviour of a phase tap changer. This is a base class for the symmetrical and asymmetrical phase tap changer models. The details of these models can be found in IEC 61970-301.
*NOTE: this is an abstract class and should not be instantiated directly
URI: cim:PhaseTapChangerNonLinear
Type: Class
Inheritance
- IdentifiedObject
- PowerSystemResource
- TapChanger
- PhaseTapChanger
- PhaseTapChangerNonLinear
- PhaseTapChanger
- TapChanger
- PowerSystemResource
Attributes
| Name | URI | Cardinality and Range | Inheritance | Description |
|---|---|---|---|---|
| voltageStepIncrement | cim:PhaseTapChangerNonLinear.voltageStepIncrement | 1..1 PerCent | direct | The voltage step increment on the out of phase winding (the PowerTransformerEnd where the TapChanger is located) specified in percent of rated voltage of the PowerTransformerEnd. A positive value means a positive voltage variation from the Terminal at the PowerTransformerEnd, where the TapChanger is located, into the transformer.When the increment is negative, the voltage decreases when the tap step increases. |
| xMax | cim:PhaseTapChangerNonLinear.xMax | 1..1 Reactance | direct | The reactance depends on the tap position according to a u shaped curve. The maximum reactance (xMax) appears at the low and high tap positions. Depending on the āuā curve the attribute can be either higher or lower than PowerTransformerEnd.x. |
| xMin | cim:PhaseTapChangerNonLinear.xMin | 0..1 Reactance | direct | The reactance depend on the tap position according to a u shaped curve. The minimum reactance (xMin) appear at the mid tap position. PowerTransformerEnd.x shall be consistent with PhaseTapChangerLinear.xMin and PhaseTapChangerNonLinear.xMin. In case of inconsistency, PowerTransformerEnd.x shall be used. |
| TransformerEnd | cim:PhaseTapChanger.TransformerEnd | 1..1 TransformerEnd | PhaseTapChanger | Transformer end to which this phase tap changer belongs. |
| highStep | cim:TapChanger.highStep | 1..1 integer | TapChanger | Highest possible tap step position, advance from neutral.The attribute shall be greater than lowStep. |
| lowStep | cim:TapChanger.lowStep | 1..1 integer | TapChanger | Lowest possible tap step position, retard from neutral. |
| ltcFlag | cim:TapChanger.ltcFlag | 1..1 boolean | TapChanger | Specifies whether or not a TapChanger has load tap changing capabilities. |
| neutralStep | cim:TapChanger.neutralStep | 1..1 integer | TapChanger | The neutral tap step position for this winding.The attribute shall be equal to or greater than lowStep and equal or less than highStep.It is the step position where the voltage is neutralU when the other terminals of the transformer are at the ratedU. If there are other tap changers on the transformer those taps are kept constant at their neutralStep. |
| neutralU | cim:TapChanger.neutralU | 1..1 Voltage | TapChanger | Voltage at which the winding operates at the neutral tap setting. It is the voltage at the terminal of the PowerTransformerEnd associated with the tap changer when all tap changers on the transformer are at their neutralStep position. Normally neutralU of the tap changer is the same as ratedU of the PowerTransformerEnd, but it can differ in special cases such as when the tapping mechanism is separate from the winding more common on lower voltage transformers.This attribute is not relevant for PhaseTapChangerAsymmetrical, PhaseTapChangerSymmetrical and PhaseTapChangerLinear. |
| normalStep | cim:TapChanger.normalStep | 1..1 integer | TapChanger | The tap step position used in normal network operation for this winding. For a Fixed tap changer indicates the current physical tap setting.The attribute shall be equal to or greater than lowStep and equal to or less than highStep. |
| TapChangerControl | cim:TapChanger.TapChangerControl | 0..1 TapChangerControl | TapChanger | The regulating control scheme in which this tap changer participates. |
| mRID | cim:IdentifiedObject.mRID | 1..1 string | IdentifiedObject | Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
| description | cim:IdentifiedObject.description | 0..1 string | IdentifiedObject | The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
| energyIdentCodeEic | eu:IdentifiedObject.energyIdentCodeEic | 0..1 string | IdentifiedObject | The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. For details on EIC scheme please refer to ENTSO-E web site. |
| name | cim:IdentifiedObject.name | 1..1 string | IdentifiedObject | The name is any free human readable and possibly non unique text naming the object. |
| shortName | eu:IdentifiedObject.shortName | 0..1 string | IdentifiedObject | The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. |
Schema Source
- from schema: http://ucaiug.org/ns/CGMES/CoreEquipment-EU/3.0