NonlinearShuntCompensator
A non linear shunt compensator has bank or section admittance values that differ. The attributes g, b, g0 and b0 of the associated NonlinearShuntCompensatorPoint describe the total conductance and admittance of a NonlinearShuntCompensatorPoint at a section number specified by NonlinearShuntCompensatorPoint.sectionNumber.
URI: cim:NonlinearShuntCompensator
Type: Class
%%{init: {'theme':'base','themeVariables': {'lineColor': '#FF0000'}}}%%
classDiagram
class NonlinearShuntCompensator
click NonlinearShuntCompensator href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/NonlinearShuntCompensator/"
style NonlinearShuntCompensator fill:#102820,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
ShuntCompensator <|-- NonlinearShuntCompensator : inherits
click ShuntCompensator href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/ShuntCompensator/"
style ShuntCompensator fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
RegulatingCondEq <|-- ShuntCompensator : inherits
click RegulatingCondEq href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/RegulatingCondEq/"
style RegulatingCondEq fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
EnergyConnection <|-- RegulatingCondEq : inherits
click EnergyConnection href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/EnergyConnection/"
style EnergyConnection fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
ConductingEquipment <|-- EnergyConnection : inherits
click ConductingEquipment href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/ConductingEquipment/"
style ConductingEquipment fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
Equipment <|-- ConductingEquipment : inherits
click Equipment href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/Equipment/"
style Equipment fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
PowerSystemResource <|-- Equipment : inherits
click PowerSystemResource href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/PowerSystemResource/"
style PowerSystemResource fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
IdentifiedObject <|-- PowerSystemResource : inherits
click IdentifiedObject href "/Models/Profiles/SteadyStateHypothesis/ConcreteClasses/IdentifiedObject/"
style IdentifiedObject fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white
ShuntCompensator : ShuntCompensator.sections
RegulatingCondEq : RegulatingCondEq.controlEnabled
Equipment : Equipment.inService
IdentifiedObject : IdentifiedObject.mRID
Inheritance
- IdentifiedObject
- PowerSystemResource
- Equipment
- ConductingEquipment
- EnergyConnection
- RegulatingCondEq
- ShuntCompensator
- NonlinearShuntCompensator
- ShuntCompensator
- RegulatingCondEq
- EnergyConnection
- ConductingEquipment
- Equipment
- PowerSystemResource
Attributes
| Name | URI | Cardinality and Range | Description | Inheritance |
|---|---|---|---|---|
| sections | cim:ShuntCompensator.sections | No cardinality available float | Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input. | |
| For LinearShuntConpensator the value shall be between zero and ShuntCompensator.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values. | ||||
| For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPoint-s. | ShuntCompensator | |||
| controlEnabled | cim:RegulatingCondEq.controlEnabled | No cardinality available boolean | Specifies the regulation status of the equipment. True is regulating, false is not regulating. | RegulatingCondEq |
| inService | cim:Equipment.inService | No cardinality available boolean | Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model. | Equipment |
| mRID | cim:IdentifiedObject.mRID | No cardinality available string | Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. | |
| For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. | IdentifiedObject |