Skip to content

ConformLoad

ConformLoad represent loads that follow a daily load change pattern where the pattern can be used to scale the load with a system load.

URI: cim:ConformLoad
Type: Class

ConformLoad class diagram

Inheritance

Attributes

Name URI Cardinality and Range Inheritance Description
p cim:EnergyConsumer.p 1..1 ActivePower EnergyConsumer Active power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.For voltage dependent loads the value is at rated voltage.Starting value for a steady state solution.
q cim:EnergyConsumer.q 1..1 ReactivePower EnergyConsumer Reactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.For voltage dependent loads the value is at rated voltage.Starting value for a steady state solution.
inService cim:Equipment.inService 1..1 boolean Equipment Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
mRID cim:IdentifiedObject.mRID 1..1 string IdentifiedObject Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Format Examples

{
    "@context": {"rdf": "http://www.w3.org/1999/02/22-rdf-syntax-ns#", "linkml": "https://w3id.org/linkml/", "sh": "http://www.w3.org/ns/shacl#", "skos": "http://www.w3.org/2004/02/skos/core#", "dc": "http://purl.org/dc/elements/1.1/", "profcim": "http://iec.ch/TC57/ns/CIM/prof-cim#", "owl": "http://www.w3.org/2002/07/owl#", "cim": "http://iec.ch/TC57/CIM100#", "cims": "http://iec.ch/TC57/1999/rdf-schema-extensions-19990926#", "dct": "http://purl.org/dc/terms/", "this": "http://ucaiug.org/ns/CGMES/SteadyStateHypothesis-EU/3.0#", "rdfs": "http://www.w3.org/2000/01/rdf-schema#", "dcat": "http://www.w3.org/ns/dcat#", "eu": "http://iec.ch/TC57/CIM100-European#"},
    "@id": "urn:uuid:<uuid>",
    "@type": "cim:ConformLoad",
    "cim:EnergyConsumer.p": "float",
    "cim:EnergyConsumer.q": "float",
    "cim:Equipment.inService": "boolean",
    "cim:IdentifiedObject.mRID": "string"
}
<cim:ConformLoad rdf:ID="_<uuid>">
    <cim:EnergyConsumer.p>float</cim:EnergyConsumer.p>
    <cim:EnergyConsumer.q>float</cim:EnergyConsumer.q>
    <cim:Equipment.inService>boolean</cim:Equipment.inService>
    <cim:IdentifiedObject.mRID>string</cim:IdentifiedObject.mRID>
</cim:ConformLoad>
{
    "p": "float",
    "q": "float",
    "inService": "boolean",
    "mRID": "string"
}
<urn:uuid:<graph-id>> {
    <urn:uuid:<uuid>>
        a cim:ConformLoad ;
        cim:EnergyConsumer.p "float" ;
        cim:EnergyConsumer.q "float" ;
        cim:Equipment.inService "boolean" ;
        cim:IdentifiedObject.mRID "string" .
}

Schema Source