Skip to content

SynchronousMachine

An electromechanical device that operates with shaft rotating synchronously with the network. It is a single machine operating either as a generator or synchronous condenser or pump.

URI: cim:SynchronousMachine
Type: Class

%%{init: {'theme':'base','themeVariables': {'lineColor': '#FF0000'}}}%%
classDiagram
    class SynchronousMachine
    click SynchronousMachine href "/Models/Profiles/ShortCircuit/ConcreteClasses/SynchronousMachine/"
    style SynchronousMachine fill:#102820,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        RotatingMachine <|-- SynchronousMachine : inherits
            click RotatingMachine href "/Models/Profiles/ShortCircuit/AbstractClasses/RotatingMachine/"
            style RotatingMachine fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        RegulatingCondEq <|-- RotatingMachine : inherits
            click RegulatingCondEq href "/Models/Profiles/ShortCircuit/AbstractClasses/RegulatingCondEq/"
            style RegulatingCondEq fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        EnergyConnection <|-- RegulatingCondEq : inherits
            click EnergyConnection href "/Models/Profiles/ShortCircuit/AbstractClasses/EnergyConnection/"
            style EnergyConnection fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        ConductingEquipment <|-- EnergyConnection : inherits
            click ConductingEquipment href "/Models/Profiles/ShortCircuit/AbstractClasses/ConductingEquipment/"
            style ConductingEquipment fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        Equipment <|-- ConductingEquipment : inherits
            click Equipment href "/Models/Profiles/ShortCircuit/AbstractClasses/Equipment/"
            style Equipment fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        PowerSystemResource <|-- Equipment : inherits
            click PowerSystemResource href "/Models/Profiles/ShortCircuit/AbstractClasses/PowerSystemResource/"
            style PowerSystemResource fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        IdentifiedObject <|-- PowerSystemResource : inherits
            click IdentifiedObject href "/Models/Profiles/ShortCircuit/AbstractClasses/IdentifiedObject/"
            style IdentifiedObject fill:#8F9779,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white


        SynchronousMachine --> ShortCircuitRotorKind : SynchronousMachine.shortCircuitRotorType

        ShortCircuitRotorKind
            click ShortCircuitRotorKind href "/Models/Profiles/ShortCircuit/Enumerations/ShortCircuitRotorKind/"
            style ShortCircuitRotorKind fill:#4D2D18,stroke:#333,stroke-width:2px,rx:10,ry:10,color:white

        SynchronousMachine : SynchronousMachine.earthing
        SynchronousMachine : SynchronousMachine.earthingStarPointR
        SynchronousMachine : SynchronousMachine.earthingStarPointX
        SynchronousMachine : SynchronousMachine.ikk
        SynchronousMachine : SynchronousMachine.mu
        SynchronousMachine : SynchronousMachine.x0
        SynchronousMachine : SynchronousMachine.r0
        SynchronousMachine : SynchronousMachine.x2
        SynchronousMachine : SynchronousMachine.r2
        SynchronousMachine : SynchronousMachine.r
        SynchronousMachine : SynchronousMachine.satDirectSubtransX
        SynchronousMachine : SynchronousMachine.satDirectSyncX
        SynchronousMachine : SynchronousMachine.satDirectTransX
        SynchronousMachine : SynchronousMachine.shortCircuitRotorType
        SynchronousMachine : SynchronousMachine.voltageRegulationRange
        IdentifiedObject : IdentifiedObject.mRID

Inheritance

Attributes

Name URI Cardinality and Range Description Inheritance
earthing cim:SynchronousMachine.earthing No cardinality available boolean Indicates whether or not the generator is earthed. Used for short circuit data exchange according to IEC 60909. direct
earthingStarPointR cim:SynchronousMachine.earthingStarPointR No cardinality available Resistance Generator star point earthing resistance (Re). Used for short circuit data exchange according to IEC 60909. direct
earthingStarPointX cim:SynchronousMachine.earthingStarPointX No cardinality available Reactance Generator star point earthing reactance (Xe). Used for short circuit data exchange according to IEC 60909. direct
ikk cim:SynchronousMachine.ikk No cardinality available CurrentFlow Steady-state short-circuit current (in A for the profile) of generator with compound excitation during 3-phase short circuit.
- Ikk=0: Generator with no compound excitation.
- Ikk<>0: Generator with compound excitation.
Ikk is used to calculate the minimum steady-state short-circuit current for generators with compound excitation.
(4.6.1.2 in IEC 60909-0:2001).
Used only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001). direct
mu cim:SynchronousMachine.mu No cardinality available float Factor to calculate the breaking current (Section 4.5.2.1 in IEC 60909-0).
Used only for single fed short circuit on a generator (Section 4.3.4.2. in IEC 60909-0). direct
x0 cim:SynchronousMachine.x0 No cardinality available Reactance Zero sequence reactance of the synchronous machine. direct
r0 cim:SynchronousMachine.r0 No cardinality available Resistance Zero sequence resistance of the synchronous machine. direct
x2 cim:SynchronousMachine.x2 No cardinality available Reactance Negative sequence reactance. direct
r2 cim:SynchronousMachine.r2 No cardinality available Resistance Negative sequence resistance. direct
r cim:SynchronousMachine.r No cardinality available Resistance Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909. direct
satDirectSubtransX cim:SynchronousMachine.satDirectSubtransX No cardinality available PU Direct-axis subtransient reactance saturated, also known as Xd"sat. direct
satDirectSyncX cim:SynchronousMachine.satDirectSyncX No cardinality available PU Direct-axes saturated synchronous reactance (xdsat); reciprocal of short-circuit ration. Used for short circuit data exchange, only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001). direct
satDirectTransX cim:SynchronousMachine.satDirectTransX No cardinality available PU Saturated Direct-axis transient reactance. The attribute is primarily used for short circuit calculations according to ANSI. direct
shortCircuitRotorType cim:SynchronousMachine.shortCircuitRotorType No cardinality available ShortCircuitRotorKind Type of rotor, used by short circuit applications, only for single fed short circuit according to IEC 60909. direct
voltageRegulationRange cim:SynchronousMachine.voltageRegulationRange No cardinality available PerCent Range of generator voltage regulation (PG in IEC 60909-0) used for calculation of the impedance correction factor KG defined in IEC 60909-0.
This attribute is used to describe the operating voltage of the generating unit. direct
mRID cim:IdentifiedObject.mRID No cardinality available string Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. IdentifiedObject

Schema Source